Chapter 1: What is RS 422, RS 485, comparison with RS
232.
RS 232 is well-known due to popularity of today's PC's, unlike the
RS422 and RS 485. These are used in industry for control systems and data
transfers (small volumes, NO hundreds of Mb/s).
So, what is the main difference between RS 232 and RS 422 & 485?
The RS 232 signals are represented by voltage levels with respect to
ground. There is a wire for each signal, together with the ground signal
(reference for voltage levels). This interface is useful for
point-to-point communication at slow speeds. For example, port COM1 in a
PC can be used for a mouse, port COM2 for a modem, etc. This is an example
of point-to-point communication: one port, one device. Due to the way the
signals are connected, a common ground is required. This implies limited
cable length - about 30 to 60 meters maximum. (Main problems are
interference and resistance of the cable.) Shortly, RS 232 was designed
for communication of local devices, and supports one transmitter and one
receiver.
RS 422 & 485 uses a different principle: Each signal uses one
twistedpair (TP) line - two wires twisted around themselves. We're talking
'Balanced data transmission', or 'Differential voltage transmission'.
Simply, let's label one of the TP wires 'A' and the other one 'B'. Then,
the signal is inactive when the voltage at A is negative and the voltage
at B is positive. Otherwise, the signal is active, A is positive and B is
negative. Of course, the difference between the wires A and B matters. For
RS 422 & 485 the cable can be up to 1200 meters (4000 feet) long, and
commonly available circuits work at 2.5 MB/s transfer rate.
What is the difference between RS 422 and RS 485? Electrical principle
is the same: both use differential transmitters with alternating voltages
0 and 5V. However, RS 422 is intended for point-to-point communications,
like RS 232. RS 422 uses two separate TP wires, data can be transferred in
both directions simultaneously. RS 422 is often used to extend a RS 232
line, or in industrial environments.
RS 485 is used for multipoint communications: more devices may be
connected to a single signal cable - similar to e.g. ETHERNET networks,
which use coaxial cable. Most RS 485 systems use Master/Slave
architecture, where each slave unit has its unique address and responds
only to packets addressed to this unit. These packets are generated by
Master (e.g. PC), which periodically polls all connected slave
units.
This article will mainly cover the Master/Slave architecture because it
is sufficient for 95% of applications. In special cases (security systems,
...), an improved version of multiprocessor communication is used. This
system uses only a single line for bidirectional communication; however,
there is no Master. All units announce a packet transmission of a
specified length, and at the same time listen whether the data has been
successfully transmitted. If it's not the case, they stop communicating
and listen for what has happened. At this time, urgent packets can be
transmitted over the line. This system is ideal for devices, that need to
immediately transfer some very important and up-to-date data, without
waiting for Master to give them a chance to do so. On the other side,
useful data transfer is less effective (about 30% less effective than the
first system). In Master/Slave architecture, slave never
starts the communication. It is critical for Master to send correct
addresses.
RS 485 exists in two versions: 1 TwistedPair or 2 TwistedPairs.
- Single TwistedPair RS 485
In this version, all devices are
connected to a single TwistedPair. Thus, all of them must have drivers
with tri-state outputs (including the Master). Communication goes over
the single line in both directions. It is important to prevent more
devices from transmitting at once (software problem).
- Double TwistedPair RS 485
Here, Master does not have to have
tri-state output, since Slave devices transmit over the second
twistedpair, which is intended for sending data from Slave to Master.
This solution often allows to implement multipoint communication in
systems, which were originally designed (HW as well as SW) for RS232. Of
course, Master software needs to be modified, so that Master
periodically sends query packets to all Slave devices. Increased data
throughput is evident in large volumes. Sometimes you can see a RS
485 system in a point-to-point system. It is virtually identical to RS
422; the high impedance state of the RS 485 output driver is not used.
The only difference in hardware of the RS 485 and RS 422 circuits is the
ability to set the output to high impedance state.
Chapter 2: Balanced differential
signals
First, let's talk about advantages and disadvanteges of RS 422/485. For
a basic RS 422/485 system, we need an I/O driver with differential outputs
and an I/O receiver with differential inputs. Noise and interference is
introduced into the line; however, since the signal is transferred via a
twisted pair of wires, the voltage difference (between A and B) of this
interference is almost zero. Due to the differential function of the RS
422/485 input amplifier of the receiver, this interference is eliminated.
The same is true for crosstalk from neighboring lines, as well as for any
other source of interference, as long as the absolute maximum voltage
ratings of the receiver circuits are not exceeded. Differential inputs
ignore different earth potentials of the transmitter and the receiver.
This is very important for communications of diverse systems, where great
problems would otherwise arise - e.g. different power sources, etc.
TwistedPair cables, together with correct terminations (to eliminate
reflections), allow data transfer rate of over 10Mbit/s with cables up to
1 km long. However, all of these advantages come at a cost. RS
422/485 circuits are more complex, and thus more expensive. Higher data
transfer speeds require correctly connected and matched terminations,
which can be a problem in systems where the number of connected devices
changes. And, of course, TwistedPair cables are required.
In a RS 232 unbalanced data transmission system, each signal is
represented by a voltage level with respect to ground. For example, the
TxD signal of a PC COMx port is negative when idle, and switches between
positive and negative level when transmitting data. Amplitude ranges
between -15 to -5V in negative state, and between +5 to +15V in positive
state.
In a balanced differential system, the transmitter generates a voltage
between 2 to 7V (approx.) between the A and B outputs. Although the
transmitter and the receiver are connected with a ground wire (GND) as
well, it is never used to determine logic levels at the AB wires. This
implies already mentioned tolerance of different ground potentials of the
transmitter and the receiver. RS 485 transmitters have an Enable input,
allowing to set the outputs to high impedance state, allowing several
devices to share a single TP. RS 422 transmitters usually don't provide
such input. Voltage level of most commonly sold transmitters is 0 and 5V.
When idle, there is +5V on B and 0V on A.
RS422/485 receivers react to voltage difference betweeen the A and B
inputs. If Vab is greater than 200mV, a logic level is defined on the
receiver output. For Vab less than 200mV, the logic level is opposite.
Picture shows a simplified schematics of receiver input connections for
a twisted pair line, and a graph of level determination.
EIA STANDARD RS 422 & RS 485
There are two standards describing Balanced interface circuits:
EIA-RS 422 (international standard ITU-T V.11) defines
point-to-point interfaces with up to 10 receivers for a single
transmitter. The limiting parameter is the receiver input impedance
Ri=4kOhm. 10 receivers + termination resistor 100 Ohm give the maximum
transmitter load.
EIA-RS 485 (ISO 8482) defines the input impedance of RS 485
circuits Ri = 12kOhm. Then, up to 32 transmitters, receivers, or
combination, can be connected to a single line. Since the data transfer is
bidirectional, the line needs to have a terminating resistor at both ends.
This picture
compares the standards RS 485 and RS 422, summarizes individual values and
shows connections of termination resistors.
Ground potential difference between different devices is +- 7V max,
according to EIA-RS 422. EIA-RS 485 defines maximum voltage range at the
receiver input (ground potential difference + alternating signal voltage)
from -7V to +12V. RS 422/482 circuits have a short-circuit protection.
Point-to-point (EIA-RS 422) defines short circuit as a current greater
than 150mA, between A and B or against the ground. Multipoint (EIA-RS 485)
defines short circuit as current greater than 150mA against the ground, or
more than 250 mA between A and B.
Ground connection for RS 422/485
For correct operation of the transmitter and the receiver, a return
signal path between the grounding of individual devices is required. It
may be realised either by a third wire, or by grounding each device (third
pole in the mains socket). If a third (ground) wire is used, resistors
(approx. 1kOhm) should be connected in series to eliminate unwanted
currents resulting from ground potential differences.
Chapter 3: Terminations, capacities, cable lengths,
data transfer speed
RS 422/485 line termination is essential, especially for faster data
transfer rates and long cables. Main reasons for correct termination are
reflections at the ends of the line, and the minimum transmitter load
requirement. For RS 422, the termination is fairly simple (see picture
comparing RS 422 and RS 485). A terminating resistor of 100Ohm is
connected to the end of the line. If there are more RS 422 receivers
connected to the line, the resistor can be a little bigger. The value can
be calculated since the input impedance of the receivers is known.
For RS 485, the termination is somewhat more complex (again, see the
comparison picture). Since each device communicates bidirectionally
(single TP version), we are unable to determine where is the transmitter
and where is the receiver - this changes constantly, according to which
device transmits at the moment. So, both ends of the line have to be
terminated with a 100Ohm terminator. However, it is not that easy. Since
all device have tri-state outputs, situations occur (very often - every
time the transmitting device or data direction changes), when all
transmitters are in high impedance state, and the line, due to termination
resistors, is in undefined state (Vab%lt;200mV). It is, however, desirable
to define idle state in this situation (Vab<-200mV). The comparison
picture shows a circuit solving this problem with termination resistor
values. The values are calculated to allow maximum number of devices (32)
with input impedances 12kOhm to be connected to a single line. It is
important that there are only two Rt resistors at the end of the cable
(they may be inside the last device connected).
Maximum data transfer speeds
Graph showing the dependence of transfer speed on several
basic conditions.
1) Maximum data transfer rate over short distances, where the line
influence can be neglected, is determined by the output parameters of the
transmitter. The duration of the rising and falling edges matters.
Standard assumes speed of 10Mbit/s; today's fastest chips, e.g.
SN76ALS176, can achieve up to 25 MBit/s.
2) When the line length exceeds 10m, we have to take into consideration
losses caused by capacities and the so-called skin effect, when the
current begins to flow only on the surface of the conductors. The rule for
standart TP cables says, that data transfer speed (Mbit/s) multiplied by
cable length (m) is less than 10^8. So, for example, if a cable is 100m
long, we get maximum data transfer speed of 1Mbit/s.
3) Last limitation applies to very long cables. Speed is limited by the
ohmic resistance of the line, and following the signal loss. Maximum cable
length is determined by its resistance, which should be less than the line
impedance - 100Ohm. Standard TP cable, diameter 2x0.6mm has a resistance
of arround 100W/Km. Capacity of the cable needs to be considered as well.
This table is for orientation only, but still very useful:
Data transfer speed |
1200bd |
2400bd |
4800bd |
9600bd |
19200bd |
38400bd |
57600bd |
115200bd |
Max. cable capacity |
250nF |
120nF |
60nF |
30nF |
15nF |
750pF |
500pF |
250pF |
Chapter 4: Protocols, software
This chapter is short because software is custom-designed for each
individual application, including the transfer protocols. RS 422, as a
point-to-point connection, operates similarly to the RS 232 serial port.
However, there are certain things software needs to take into account.
First, the communication media (TP line) needs to be assigned to
individual stations, so that there are no collisions and that responses
are fast enough.
We have to be aware of the fact, that only a single channel is
available for communication. It has to transfer both data and the bit and
byte synchronisation. For transferring of individual bits, one of the data
network modulations can be used, e.g. coding NRZ, NRZI, phase modulation
NRZ, or differential phase modulation. These modulations are not covered
in this article, they are a topic of network and protocol theory.
For byte synchronisation, several options are available. Maybe the
simplest is to reserve one byte to be a sync character. Software then
needs to convert data bytes equal to the sync byte to a sequence of
different bytes. Or, protocols SLDC/HLDC, suitable for high-speed
transfers, may be used. When an application requires only slower data
transfer rates (115200bd, or up to 2Mb/s with special UART circuits), we
can take advantage of the RS 232 format for both bit and byte
synchronisation. This solution saves a lot of effort, especially when a PC
is used as Master, and Slave is equipped with a microcontroller containing
its own UART, e.g. 8051 compatibles.
From a network point of view, the RS 485 incorporates a bus topology.
Since Slave stations have no means of starting the communication without a
risk of collision, they need to be assigned a 'right to transmit' by the
Master station. Assignment is done centrally via pooling, where the
central (Master) station periodically asks all Slaves whether they have
data to transmit. If so, the questioned station sends the data
immediately; otherwise, it replies with a confirmation packet only, or
does not reply at all. This method is good for Multipoint systems with
smaller number of Slave stations (approx. up to 100). For more stations,
the reply would become too slow. Of course, individual system requirements
need to be considered. Mentioned 100 stations is for an "on-line" system,
where stations have to interactively react to user requests, thus the
reply delay needs to be less than 0.5 sec (considered for 115200bd data
transfer rate, which is seldom available in industrial
environments).
Of course, in systems where the Master has no priority function, or due
to other factors (e.g. large number of stations with low frequency of data
transfers), different access methods may be used. For example, the random
access method ALOHA. Here, any station sends its data regardless of the
transfer channel status. If a collision occurs, the station does not
receive a confirmation, and repeats transmission. However, this method
utilises on average only about 18% of available bandwidth, and with larger
volumes of data the throughput decreases rapidly due to larger number of
collisions. With RS 485, where transmitters can at the same time "listen"
for the channel status, the ALOHA method can be improved by a "carrier"
(data activity) detection. In this case, stations begin transmission only
if the channel is idle. Both methods essentially require a transfer
protocol with error detection.
In any data transfer, including the RS 485, there is no way to 100%
guarantee that a transmitted packet has been successfully received.
Especially with the ALOHA methods, collisions may occur; interference,
cable length, etc. causes errors too. It is advisable for the
communication software to take such situations into consideration. In the
central assignment method it is useful for slave stations to send a reply
packet with information of last packet received. Several options are
available, choice depends on individual use.
Chapter 5: More than 32 nodes, handy tips, recommended
parts
In case an application requires more than 32 devices, there are
basically two options. The simpler is to use transmitters with 4 times the
input impedance (48k), allowing to connect up to 128 devices at the same
time; these are commonly available nowadays. In this case, we have to
adapt the whole termination system. The other option is to use a RS 485
repeater. Such a device has two TP ports. When data appear on one of them,
the repeater sends them to the other port, and vice versa. In this way, we
can connect another 31 (or 127) stations. Data activity detection can be
very simple, using the RS 485 definition - Vab>200mV; or, such a
repeater may incorporate its own processor and work as a router as well -
like in computer networks.
One of the last things I'll mention are commonly available parts for RS
422/485. I have had personal experience with circuits made by MAXIM; they
make about ten versions - differences are in speed (0.25 or 2.5 Mbit/s),
operation type (half/full duplex), number of devices (32, 128), and in
several other parameters. They are labeled MAX481, 485, 487, 491 and so
on. Another manufacturer is National Semiconductors, label DS3695A. I
assume that every major manufacturer offers some circuits for RS 422/485;
however, I don't know any details. Some info in this article comes from
excellent publication by Texas Instruments, who make a whole family of RS
422/485 circuits labelled SN 7517X, where X is one- or two-digit type
specification.
Several hints:
- Don't know which wire is A and B? When idle, B is more
positive than A.
- You don't always have to use TP cables. For small distances
and low speeds, common telephone cables are good enough.
- Termination is not critical for small distances and low speeds
- works fine with MAX circuits.
- In Czech Republic, MAX487 is available at Starmans Electronic,
or Spezial electronics for less than 100 KPhi (approx. $4). For other
countries, please contact your local electronic components dealer.
Final words
The decision of suitability or unsuitability of RS 422/485 for your
application is up to you. I hope that this article has provided you with
enough basic info. If you are in the process
of deciding which type of communication to use in your project, then I
hope that this article has brought an inspiration and perhaps saved a lot
of time and effort. Of course, if you are interested, you can contact me
via e-mail.